As the professional manufacture, we would like to provide you 40A High-Voltage DC Relay.
●40A continuous current-carrying capacity at 85 °C ●Ceramic-sealed contacts, IP67-rated ●Insulation resistance: 1000 MΩ (at 1000 VDC); dielectric strength between contacts and coil of 4 kV, IEC 60664-1 compliantAs a professional high quality 40A High-Voltage DC Relay manufacture, you can rest assured to buy it from our factory and we will offer you the best after-sale service and timely delivery.
■ The contact part is ceramic-sealed and can meet the IP67 protection rating.
■ The insulation resistance is up to 1000 MΩ (1000 VDC), and the dielectric withstand voltage between the contact and the coil is up to 4 kV, IEC 60664-1 compliant.
■ Used for high-voltage DC switching circuits in energy storage.
1 Part number NFGP40
2 Load voltage(V) 1500:1500VDC
3 Coil voltage(V) DC:12,24
4 Contact arrangement H:1 Form A
5 Coil connection C:Connentor
6 Load connection 5:Internal thread
|
Contact Arrangement |
1H |
|
Contact Material |
Copper Alloy |
|
Contact Rating |
40A |
|
Min. Applicable Load |
1A/12VDC |
|
Max. Breaking Current |
400A/300VDC( ≥ 1cycle) |
|
Rated Load Voltage |
1500VDC |
|
Contact Resistance |
≤5mΩ (40A) |
|
Electrical Endurance (Breaking) |
≥ 3 × 10² (40A /1500VDC ON OFF=0.6s:5.4s) |
|
Mechanical Endurance |
≥ 2 × 10⁵ |
Coil Parameter¹
|
Coil voltage VDC |
Coil resistance Ω ±10% |
Pick-up voltage VDC |
Drop-out voltage VDC |
Max. allowable voltage VDC |
Coil power W |
Operate time ms |
Release time ms |
|
12 |
48 |
≤9 |
≥ 1 |
18 |
3 |
≤ 30 |
≤ 10 |
|
24 |
192 |
≤ 18 |
≥2 |
36 |
Notes¹. Standards test condition :
Temperature: (23±5)℃
Humidity: (25%~75%)RH
Direction of measurement: Terminalsup position is standard position
|
Insulation Resistance |
1000MΩ (1000VDC) |
|
|
Dielectric Strength |
3000VAC(50Hz,1min) Leak Current 1mA |
|
|
Vibration Resistance |
10Hz~500Hz 49m/s² |
|
|
Shock Resistance |
Stability |
ON: 98m/s², Half Sine 11ms, Testing Time:10s |
|
Durability |
490m/s², Half Sine 6ms |
|
|
Operating Ambiance Temperature² |
-40℃ ~ 85℃ |
|
|
Operating Ambiance Humidity |
5%~85% (No ice or Frosting) |
|
|
Pressure |
86kPa ~ 106kPa |
|
|
Weight (Approx.) |
165g |
|
Notes². The product storage locationshall not be exposed to corrosive gas. Avoid direct sunlight on the products.

1.The relay is a high-voltage DC switching device. In the final fault state, it may not be able to connect or cut off. Once the product cannot be cut off, may lead to abnormal heat and smoke, fire or other accidents. Therefore, please avoid the use of the above specifications
(including but not limited to coil rating, load ratings and electrical life, etc.) .Please use a circuit that can quickly cut off the load In an emergency. To ensure safety, the product should be replaced regularly.
2.Contacts rating is the value under resistive load. Please take measures of surge absorption device together with inductive load when using the L/R ≥ 1ms inductive load (L load),otherwise it may lead to the decrease of electrical endurance and defective switch.
3. It is recommended to install the nonlinear resistance (recommend using variable resistance) in order to suppress the reverse electromotive force of coil. But please do not use diode, otherwise it will lead to the decline of relay performance.
4. It is strictly prohibited to place the relay for a long time in the environment beyond the operating temperature (-40 85 ℃ ) of the product.
5.Please do not install the product in a strong magnetic field (the periphery of a transformer, or magnet) or near the heating object.
6. In order to prevent looseness, please use the gaskets correctly when installing the relay. Please use M6 screws to install therelay, the locking torque should be controlled within 6N.m ~ 8N.m; The locking torque of M4 mounting nuts on the terminals should be controlled within 2N.m ~ 3N.m .The product maybe damaged in the case of excessive torque.
7.Please avoid grease and other foreign matter attached to the terminals. Please use the connection wire above 10mm2 spec, otherwise it may lead to abnormal heating of the terminals.
8.Please use the specified connector When connecting to the connector.9. In principle, please do not use it when the relay has fallen down.